Online Double Conversion, transformer base 3/1 technology with stable and uninterrupted power and complete sine waveform linear and non-linear loads at maximum load consumption
Suitable for all kinds of loads (resistive, inductive and non-linear loads etc)
DSP (digital signal processors )control technology Effective software and hardware protection
Device dimensions: 400mm width, 815mm depth, 1100mm height (400×815×1100mm)
Net weight of the device: 210 kg
Standard configuration with isolation transformer
Protection: short circuits, high and low voltages, overload, reverse connection of batteries and High charge, etc.
LCD display to show input and output voltage, load, frequency, inside temperature of the device,battery charge load
Adjusting the output voltage ,EOD, automatic start, bypass mode and adjusting the frequency and ECO MODE through the LCD display panel
Select current charging : 2A / 4A / 6A / 8A / 10A / 12A
Output Power factor of 0.8 & Input power factor 0.99 and Active Power Factor Correction (Apfc)
Overload capacity up to 105% ~ 125% for 10 min, 125% ~ 150% for 1 min ,150%~200% for 200 ms, UP to 200%for 100 ms
Wide input frequency range for operation with variety of generators in the range of 40 to 70 Hz and proper stabilization of the output frequency of 50 Hz with a telorance of 0.1
Connecting to Parallel card
Communication with PC by RS232 (standard), USB / RS485 / SNMP / Dry Call (optional)
Adjusting the output frequency at 50 and 60 Hz and having Auto frequency Sensing
Cold Start and automatic start-up after connecting the city electricity and having settable delay
Shut down automatically in emergency time (EPO)